CO2 SYSTEM - BATAM





Concentration Test > Functional Tests > operation of the discharge valve or pneumatic/ electrical discharge devices should be verified.
Annually. a functional test of the control/protection circuits should be performed.Electrical  discharge  devices should be verified. > Alarms and Beacons function test > Signage. To advise personnel of the risk of CD2 systems in the vicinity. appropriate warning signs must be affixed in conspicuous locations > Changing and Filling. Cylinder outlets should be fitted with safety covers or antirecoil devices. whenever the cylinderis not connected to the system piping.
(or spares) without discharging may be permitted to be retained in service for a maximum of 12 years from the date of the last hydrostatic test. At the end of 12 years. they must be discharged and retested befare being returned to service
The vapor phase shall not be less than 88.5 percent carbon dioxide > Weighing. High-pressure CD2 cylindersmust be weighed
semiannually to verify that the proper volume of gas is available. Containers showing a loss in net content of more than ID percent must be refilled or replaced > Testing. High-pressure CD2 cylinders must not be recharged without a hydrostatic test (and remarking) if more than 5 years have elapsed from the date of the last test. Cylinders continuously in service.

OFFICE
Ruko Siriaon Indah Blok B no: 2-3. Patam Lestari Sekupang, Batam post code 29428 Kepulauan Riau. Indonesia.
Contact.
Phone : 062-778-3540263
Fax : 062-778-3540263
Email : marketing@ecp-batam.com.

Electrical System – Automation - Batam

Electrical System – Automation




Trading and distribution of control and automation components has been the core business of SCL Distribution business for control and automation components. Distributing and representing numerous international brands. Some notable brands under our care include Q-Light, Upun, i-Wire, i-Bon, Switchwell, and Boxco.



Product Range

      




Visit Us

Addressable Fire Alarm Control Panel - Batam

Addressable Fire Alarm Control Panel


Description
The LCT-AFP2100 series control panel (linkage type) (fire alarm control panel) is a new generation product launched by ASENWARE. In order to adapt to the needs of engineering design, the fire alarm control panel is designed with a linkage control function that enables it to be flexibly used with other related products from ASENWARE to form a fire alarm and linkage integrated control system. It is particularly suitable for applications in large and medium-sized fire alarm and linkage integrated control systems.

The LCT-AFP2100 series addressable control panel is a dual wire analog bus system. It can replace the conventional fire alarm system to save 50% or more cables.

The LCT-AFP2100 series addressable control panel is an advanced, perfect and reliable system, which is designed for big porjects, has been used in many countries.
Parameter: 

Capacity:

Each loop card has 2 loops, with 324 addresses as alarm/control points of each loop, the capacity of each loop card is 324*2=648(addresses);
Each wall mounted LCT-AFP2100 panel can be installed maximum 3 loop cards, the maxium capacity is 648*3=1944(addresses). Over 1944 addresses, use the cabinet panel, the cabinet panel can be installed maxium 40 loop cards, the maximum capacity is 648*40=25920(addresses);
Peer-to-peer with max.20 LCT-AFP2100 panels, the maxium system capacity: 25920*20=518400(addresses);
Maximum simultaneous alarm of each host:

Fire alarm: 500;
Trouble: 500;
Feedback: 500.
Operating evironment:

Temperature -10℃~+55℃
Humidity ≤95%, 40℃,non-condensing
AC Power AC220V, 50HZ,3A
DC Power DC24V,7A